Loge is an AVR controller with one wire temperature sensor that will select the appropriate furnace for heat load balancing.

The following graph shows the heat required at different outside temperatures.


A small aux furnace, 125,000 BTU will be labeled H2. The normal furnace is H1. This graph indicates which algorithm is required to maximize matching the load to the furnace:

TemperatureHeaterBTU requiredBTU Avail
50 H2.565K62.5K
46H270K
40H2106K125K
35H2128K125K
30H1149K180K
25H1170K180K
20H1&H2.5190K242K
10H1&H2234K242K